Home / All / Electrical equipment / Vacuum Interrupter /

Vacuum interrupter JUCA 12KV 1250A 25KA (JUCA613) for VCB vacuum circuit breaker use from JUCRO Electric

Vacuum interrupter JUCA 12KV 1250A 25KA (JUCA613) for VCB vacuum circuit breaker use from JUCRO Electric

Vacuum interrupter JUCA 12KV 1250A 25KA  (JUCA613)  for VCB vacuum circuit breaker use from JUCRO Electric
Vacuum interrupter JUCA 12KV 1250A 25KA  (JUCA613)  for VCB vacuum circuit breaker use from JUCRO ElectricVacuum interrupter JUCA 12KV 1250A 25KA  (JUCA613)  for VCB vacuum circuit breaker use from JUCRO Electric
CategoriesVacuum Interrupter
BrandJUCRO
ModelJUCA613
Unit PriceUS $ 92 / piece
FOB portShanghai/Ningbo
Terms of PaymentL/C, Western Union, MoneyGram, T/T
Download DOCpdf icon
Update TimeMar 28,2024
Detail Information

Vacuum interrupter JUCA 12KV 1250A 25KA JUCA613 for VCB Vacuum Circuit Breaker use from JUCRO Electric.

Vacuum Interrupters accept customized order according to technical drawing or samples.
The vacuum interrupter use the wave ceramic as insulating shell, the contact material is CuCr alloy, the longitudinal magnetic field cup structure, with high breaking capacity, high insulation level, strong arc extinguishing ability, long life, small size and easy maintenance, No explosion risk, no pollution, low noise and so on.

Main Technical Parameters


Items

Value

Rated voltage

12kV

Rated current

1250A

Rated frequency

50/60Hz

Rated short circuit breaking current

25KA

Breaking operations under rated short circuit breaking current

30 times

Rated short circuit making current(peak value)

63KA

Rated withstand current(peak value)

63kA

Rated short time withstand current

25kA

Rated breaking current of single capacitor bank

#630A

Rated breaking current of back to back capacitor bank

#400A

Rated power frequency withstand voltage (1 min)

49kV

Rated lightning impulse withstand voltage

85kV

Circuit resistance at lowest rated contacts force

≤25μΩ

Mechanical life

20000 times

Closing force due to bellows and atmosphere

100±30N

Force required to hold contacts opening at full stroke

200±30N

Rated duration of short circuit

4s

Limiting abrasion of contacts

3mm

Storage life

20 years

Moving mass of interrupter

0.84kg

Rated operating sequence

O-0.3s-CO-180s-CO

 

Mechanical requiements of vacuum circuit breaker

Items

Value

Clearance between opening contacts

9±1mm

Contact connection stroke

4±1mm

Average opening speed

1.1±0.2 m/s

Average closing speed

0.6±0.2 m/s

Rated contacts pressure

2400±200N

Contacts bouncing duration at closing operation

≤3ms

Contacts re-bouncing clearance at opening operation

≤2mm

Synchronism of three phases

≤2ms


 Packing & Delivery 

Strong package, Safety first.

Inside with foam to support the product, put it in carton or wooden box, fixed it on pallet.

As long as possible to keep the products safe until it arriving customer's warehouse.

Clearly marking label outside of package, customers will be easy to identify their goods.
Our Company
20000 M2 of JUCRO Electric company land
1500 M2 of office building
5000 M2 of workshop building
Inside of JUCRO Electric office building
Inside of JUCRO Electric office building
JUCRO Electric office work area
Workshop

Vacuum Interrupter Workshop

Accept customized order.
Design the Vacuum Interrupter for you.

VCB Production Line

VCB Vacuum Circuit Breaker production Line.

VCB Production Line

VCB Vacuum Circuit Breaker production line, Engineers routine inspection.
Quality Inspection
 Carefully inspection of each product, Quality guaranteed 
 completely data records of entire process , all the product data can be traced. 
Please send your message to us
*Email
Tel
*Title
*Content
Upload
  • Only supports .rar/.zip/.jpg/.png/.gif/.doc/.xls/.pdf, maximum 20MB.

Professional production line solution provider!

MOBILE WEB
NEWSLETTER

Sign up today for hints, tips and the latest product news - plus exclusive special offers.

Tel:+0086-18131539058

subscription

We don’t do spam and Your mail id is very confidential.